An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1e900 the extracted gateway value from the xml file is used as an argument to /etc/config-tools/config_default_gateway number=0 state=enabled value=<contents of gateway node> using sprintf(). This command is later executed via a call to system().
[
{
"product": "WAGO PFC200",
"vendor": "Wago",
"versions": [
{
"status": "affected",
"version": "Firmware version 03.02.02(14)"
}
]
}
]