4.3 Medium
CVSS2
Attack Vector
NETWORK
Attack Complexity
MEDIUM
Authentication
NONE
Confidentiality Impact
NONE
Integrity Impact
NONE
Availability Impact
PARTIAL
AV:N/AC:M/Au:N/C:N/I:N/A:P
0.002 Low
EPSS
Percentile
59.2%
This updated advisory is a follow-up to the original ICS-CERT Advisory titled ICSA-12-341-01P—GE PROFICY HMI/SCADA CIMPLICITY INTEGER OVERFLOW that was published December 06, 2012, to the US-CERT secure Portal library.
Researcher Kuang-Chun Hung of Information and Communication Security Technology Center (ICST) has identified an improper input validation vulnerability in GE’s Intelligent Platforms Proficy HMI/SCADA—Cimplicity. This vulnerability could lead to a possible denial of service (DoS).
GE has produced an updated product version that ICST has validated. ICST confirms that the product update resolves the reported vulnerability.
This vulnerability can be exploited remotely.
The following products and versions are affected:
Note: Proficy HMI/SCADA—Cimplicity Versions 4.0 and prior are not affected by this vulnerability.
If exploited, this vulnerability could allow an unauthenticated remote attacker to cause the CIMPLICITY built-in Web server to crash or to stop responding to requests.
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
According to GE, Proficy HMI/SCADA—Cimplicity is a Client/Server based human-machine interface/supervisory control and data acquisition (HMI/SCADA) application deployed across multiple industries.
A vulnerability exists in the way that the CIMPLICITY built-in Web server (CimWebServer.exe) processes incoming HTTP traffic because of insufficient input validation. The CIMPLICITY built-in Web server is not enabled by default. When enabled, it listens on Port 80 TCP by default.
An attacker can exploit the vulnerability by sending malformed HTTP requests to the listening service. The attack does not require authentication and can be conducted remotely.
CVE-2012-4689NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-4689 , NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 7.1 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:N/I:N/A:C)
This vulnerability could be exploited remotely.
No known public exploits specifically target this vulnerability.
An attacker with a low skill would be able to exploit this vulnerability.
GE has released a security advisory and patches to address this issue.
Patches for versions of CIMPLICITY prior to Version 8.0 will not be created. GE recommends customers who are unable to patch or upgrade consider the recommendations below.
GE has provided the following workaround recommendations that eliminate the need to use the vulnerable component:
Option 1: Disable the CIMPLICITY built-in Web server if it is not in use.
GlobalView, WebView, and ThinView expose the existing functionality of the CIMPLICITY HMI application so that it can be viewed via a Web browser.
If this functionality is not required, Web-based access can be disabled by the following process:
Option 2: Use an alternate Web server to host GlobalView, WebView, or ThinView.
The CIMPLICITY built-in Web server can be replaced with a third-party Web application server such as Microsoft IIS.
To configure GlobalView, WebView, or ThinView to use IIS:
Important: If you would like to publish the Web page to Microsoft IIS, make sure you save the Web page to an IIS Web directory. By default, this is C:\InetPub\wwwroot or a subdirectory, but it could be another location depending on your IIS configuration. You can save the page by clicking the “Browse Page” button and navigating to the directory or by saving the file to another location and copying it to an IIS directory later.
The vulnerable service (CimWebServer.exe) will still run on the system in the “Option 2” configuration. However, because it is no longer listening on a port that is processing HTTP traffic, the vulnerability is not exposed.
As with any third-party product, ensure that your IIS Web server is up to date with the latest security patches and follow any secure configuration recommendations from the vendor.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT Web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.
Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper, ICS-TIP-12-146-01A—Targeted Cyber Intrusion Detection and Mitigation Strategy.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:N/I:N/A:C
support.ge-ip.com/support/index?page=kbchannel&id=S:KB15153
public.govdelivery.com/accounts/USDHSCISA/subscriber/new?topic_id=USDHSCISA_138
twitter.com/CISAgov
twitter.com/intent/tweet?text=GE%20Proficy%20HMI/SCADA%20Cimplicity%20Integer%20Overflow+https://www.cisa.gov/news-events/ics-advisories/icsa-12-341-01
www.dhs.gov
www.dhs.gov/foia
www.dhs.gov/performance-financial-reports
www.facebook.com/CISA
www.facebook.com/sharer/sharer.php?u=https://www.cisa.gov/news-events/ics-advisories/icsa-12-341-01&title=GE%20Proficy%20HMI/SCADA%20Cimplicity%20Integer%20Overflow
www.instagram.com/cisagov
www.linkedin.com/company/cybersecurity-and-infrastructure-security-agency
www.linkedin.com/sharing/share-offsite/?url=https://www.cisa.gov/news-events/ics-advisories/icsa-12-341-01
www.oig.dhs.gov/
www.surveymonkey.com/r/CISA-cyber-survey?product=https://www.cisa.gov/news-events/ics-advisories/icsa-12-341-01
www.usa.gov/
www.whitehouse.gov/
www.youtube.com/@cisagov
mailto:?subject=GE%20Proficy%20HMI/SCADA%20Cimplicity%20Integer%20Overflow&body=www.cisa.gov/news-events/ics-advisories/icsa-12-341-01