Siemens has identified three vulnerabilities in its SIMATIC HMI devices. These vulnerabilities were reported directly to Siemens by the Quarkslab team and Ilya Karpov from Positive Technologies. Siemens has produced updates that mitigate these vulnerabilities in most of the affected products and are preparing updates for the rest of them.
These vulnerabilities could be exploited remotely.
The following SIMATIC versions are affected:
An attacker exploiting these vulnerabilities could conduct man-in-the-middle attacks, denialβofβ service attacks, and possibly authenticate themselves as valid users.
Impact to individual organizations depends on many factors that are unique to each organization. NCCIC/ICS-CERT recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation.
Siemens is a multinational company headquartered in Munich, Germany.
SIMATIC HMI Panels, SIMATIC WinCC Runtime Advanced, and SIMATIC WinCC Runtime Professional are used for operator control and monitoring of machines and plants. SIMATIC NET PC-Software is required for communication between controller (SIMATIC S7 controller) and PC-based solutions (e.g., SIMATIC WinCC). SIMATIC WinCC is a supervisory control and data acquisition (SCADA) system. It is used to monitor and control physical processes involved in industry and infrastructure on a large scale and over long distances. SIMATIC Automation Tool allows commissioning, adjusting, and service in combination with S7-1200 and S7-1500 Controllers without engineering framework. These products are deployed across several sectors including Chemical, Energy, Food and Agriculture, and Water and Wastewater Systems. Siemens estimates that these products are used primarily in the United States and Europe with a small percentage in Asia.
Attackers with access to the network path between PLCs and their communication partners could possibly intercept or modify Siemens industrial communications at Port 102/TCP and conduct a man-in-the-middle attack. This vulnerability affects all listed products.
CVE-2015-1601NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-1601, web site last accessed April 09, 2015. has been assigned to this vulnerability. A CVSS v2 base score of 5.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:N).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:N , web site last accessed April 09, 2015.
Attackers with access to the network path between an HMI panel and a PLC (man-in-the-middle) could possibly conduct a denial-of-service attack against the HMI panel by sending specially crafted packets to the HMI (Port 102/TCP). This vulnerability affects SIMATIC WinCC Comfort Panels and SIMATIC WinCC Runtime Advanced.
CVE-2015-2822NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-2822, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 7.1 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:N/I:N/A:C).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:N/I:N/A:C, web site last accessed April 09, 2015.
If attackers obtain password hashes for SIMATIC WinCC users, they could possibly use the hashes to authenticate themselves. This vulnerability affects SIMATIC WinCC.
CVE-2015-2823NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-2823, NIST uses this advisory to create the CVE web site report. This web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:M/Au:N/C:P/I:P/A:P).CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:M/Au:N/C:P/I:P/A:P , web site last accessed April 09, 2015.
These vulnerabilities could be exploited remotely.
No known public exploits specifically target these vulnerabilities.
An attacker with medium skill level would be able to exploit these vulnerabilities.
Siemens provides updates for the following products and recommends customers update to the new fixed versions located at their cooresponding web sites listed below:
Siemens is preparing updates for the following products that will fix the vulnerabilities.
Siemens recommends either updating the configuration of SIMATIC HMI Basic Panels 2nd Generation, SIMATIC HMI Comfort Panels, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional devices configured with WinCC (TIA Portal) V12 or V13 to WinCC (TIA Portal) V13 SP1 and the devices to V13 SP1, or applying the following mitigations until patches are available.
Until new releases become available, customers should mitigate the risk of their products by implementing the following steps:
As a general security measure Siemens strongly recommends protecting network access with appropriate mechanisms. In order to run the devices in a protected IT environment, it is advised to configure the environment according to Siemensβ operational guidelines.
For more information on these vulnerabilities and detailed instructions, please see Siemens Security Advisory SSA-487246 at the following location:
<http://www.siemens.com/cert/advisories>
ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page at: http://ics-cert.us-cert.gov/content/recommended-practices. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICSβCERT Technical Information Paper, ICS-TIP-12-146-01BβTargeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site (http://ics-cert.us-cert.gov/).
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
www.industry.siemens.com/topics/global/en/industrial-security/concept/Pages/defense-in-depth.aspx
www.siemens.com/cert/advisories
cisasurvey.gov1.qualtrics.com/jfe/form/SV_9n4TtB8uttUPaM6?product=https://www.cisa.gov/news-events/ics-advisories/icsa-15-099-01
public.govdelivery.com/accounts/USDHSCISA/subscriber/new?topic_id=USDHSCISA_138
support.industry.siemens.com/cs/de/en/view/109475497
support.industry.siemens.com/cs/ww/en/view/109311423
support.industry.siemens.com/cs/ww/en/view/109311724
support.industry.siemens.com/cs/ww/en/view/109311724
support.industry.siemens.com/cs/ww/en/view/109439573
support.industry.siemens.com/cs/ww/en/view/109475388
support.industry.siemens.com/cs/ww/en/view/109475388
support.industry.siemens.com/cs/ww/en/view/98161300
twitter.com/CISAgov
twitter.com/intent/tweet?text=Siemens%20SIMATIC%20HMI%20Devices%20Vulnerabilities+https://www.cisa.gov/news-events/ics-advisories/icsa-15-099-01
www.dhs.gov
www.dhs.gov/foia
www.dhs.gov/performance-financial-reports
www.facebook.com/CISA
www.facebook.com/sharer/sharer.php?u=https://www.cisa.gov/news-events/ics-advisories/icsa-15-099-01&title=Siemens%20SIMATIC%20HMI%20Devices%20Vulnerabilities
www.instagram.com/cisagov
www.linkedin.com/company/cybersecurity-and-infrastructure-security-agency
www.linkedin.com/sharing/share-offsite/?url=https://www.cisa.gov/news-events/ics-advisories/icsa-15-099-01
www.oig.dhs.gov/
www.usa.gov/
www.whitehouse.gov/
www.youtube.com/@cisagov
mailto:?subject=Siemens%20SIMATIC%20HMI%20Devices%20Vulnerabilities&body=www.cisa.gov/news-events/ics-advisories/icsa-15-099-01