Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-19-106-02
HistoryApr 16, 2019 - 12:00 p.m.

WAGO Series 750-88x and 750-87x

2019-04-1612:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
75

7.5 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:P/A:P

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

10 High

AI Score

Confidence

High

0.054 Low

EPSS

Percentile

93.2%

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8

  • ATTENTION: Exploitable remotely/low skill level to exploit

  • Vendor: WAGO

  • Equipment: Series 750-88x and 750-87x

  • Vulnerability: Use of Hard-coded Credentials

2. RISK EVALUATION

This vulnerability allows a remote attacker to change the settings or alter the programming of the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Series 750-88x and 750-87x, programmable logic controllers, are affected:

  • Series 750-88x
    • 750-330 firmware versions prior to FW14
    • 750-352 firmware versions prior to FW14
    • 750-829 firmware versions prior to FW14
    • 750-831 firmware versions prior to FW14
    • 750-852 firmware versions prior to FW14
    • 750-880 firmware versions prior to FW14
    • 750-881 firmware versions prior to FW14
    • 750-882 firmware versions prior to FW14
    • 750-884 firmware versions prior to FW14
    • 750-885 firmware versions prior to FW14
    • 750-889 firmware versions prior to FW14
  • Series 750-87x
    • 750-830 firmware versions prior to FW06
    • 750-849 firmware versions prior to FW08
    • 750-871 firmware versions prior to FW11
    • 750-872 firmware versions prior to FW07
    • 750-873 firmware versions prior to FW07

3.2 VULNERABILITY OVERVIEW

3.2.1 USE OF HARD-CODED CREDENTIALS CWE-798

By exploiting the undocumented service access, it is possible to change the settings of a device and access web-based management with administrator privileges. An attacker can exploit this vulnerability to lock other users out from the device or open closed network ports. It is also possible to use this service access as an FTP user and exchange or delete the application.

CVE-2019-10712 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy, Transportation Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • **COMPANY HEADQUARTERS LOCATION:**United States, Germany, Switzerland, Poland, China, India

3.4 RESEARCHER

Reported by JΓΆrn Schneeweisz/Recurity Labs to CERT-Bund coordinated by CERT@VDE with NCCIC.

4. MITIGATIONS

WAGO released a security advisory available at:

<https://www.wago.com/de/download/public/Sicherheitshinweis-SA-SYS-2019-001/SA-SYS-2019-001.pdf&gt;

WAGO recommends updating to the newest firmware as listed above and taking the following defensive measures:

  • Restrict network access to the web server.
  • Restrict network access to the device.
  • Do not directly connect the device to the Internet.

CERT@VDE has published an advisory regarding this vulnerability at the following location:

<https://cert.vde.com/en-us/advisories/vde-2019-008&gt;

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

References

7.5 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:P/A:P

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

10 High

AI Score

Confidence

High

0.054 Low

EPSS

Percentile

93.2%

Related for ICSA-19-106-02