Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-22-172-06
HistoryJun 21, 2022 - 12:00 p.m.

Siemens WinCC OA

2022-06-2112:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
92

6.8 Medium

CVSS2

Attack Vector

NETWORK

Attack Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:M/Au:N/C:P/I:P/A:P

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

10 High

AI Score

Confidence

High

0.002 Low

EPSS

Percentile

54.1%

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8 *ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • **Equipment:**SIMATIC WinCC OA
  • Vulnerability: Use of Client-side Authentication

CISA is aware of a public report, known as “OT:ICEFALL” that details vulnerabilities found in multiple operational technology (OT) vendors. CISA is issuing this advisory to provide notice of the reported vulnerabilities and identify baseline mitigations for reducing risks to these and other cybersecurity attacks.

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to impersonate other users or exploit the client-server protocol without being authenticated.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of SIMATIC WinCC OA, a SCADA HMI system, are affected:

  • SIMATIC WinCC OA v3.16: All versions
  • SIMATIC WinCC OA v3.17: All versions
  • SIMATIC WinCC OA v3.18: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 USE OF CLIENT-SIDE AUTHENTICATION CWE-603

Affected applications use client-side only authentication when neither server-side authentication nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated.

CVE-2022-33139 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors

COUNTRIES/AREAS DEPLOYED: Worldwide

• ** COMPANY HEADQUARTERS LOCATION:** Germany

3.4 RESEARCHER

Daniel dos Santos and Jos Wetzels from Forecout Technologies reported this vulnerability to CISA.

4. MITIGATIONS

Siemens recommends the following mitigations or workarounds:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory SSA-111512

Remarks by ETM regarding SSA-11512 for SIMATIC WinCC OA

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/ics in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

References

6.8 Medium

CVSS2

Attack Vector

NETWORK

Attack Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:M/Au:N/C:P/I:P/A:P

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

10 High

AI Score

Confidence

High

0.002 Low

EPSS

Percentile

54.1%

Related for ICSA-22-172-06