CVSS3
Attack Vector
NETWORK
Attack Complexity
LOW
Privileges Required
NONE
User Interaction
NONE
Scope
UNCHANGED
Confidentiality Impact
NONE
Integrity Impact
NONE
Availability Impact
HIGH
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
Percentile
34.1%
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.
#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##
include('compat.inc');
if (description)
{
script_id(501615);
script_version("1.2");
script_set_attribute(attribute:"plugin_modification_date", value:"2023/10/03");
script_cve_id("CVE-2022-4608");
script_name(english:"ABB RTU500 Stack-Based Buffer Overflow (CVE-2022-4608)");
script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
script_set_attribute(attribute:"description", value:
"A vulnerability exists in HCI IEC 60870-5-104 function included in
certain versions of the RTU500 series product. The vulnerability can
only be exploited, if the HCI 60870-5-104 is configured with support
for IEC 62351-3. After session resumption interval is expired an
RTU500 initiated update of session parameters causes an unexpected
restart due to a stack overflow.
This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
# https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch
script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?382e4c09");
script_set_attribute(attribute:"solution", value:
"Refer to the vendor advisory.");
script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C");
script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H");
script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
script_set_attribute(attribute:"cvss_score_source", value:"CVE-2022-4608");
script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
script_set_attribute(attribute:"exploit_available", value:"false");
script_cwe_id(787);
script_set_attribute(attribute:"vuln_publication_date", value:"2023/07/26");
script_set_attribute(attribute:"patch_publication_date", value:"2023/07/26");
script_set_attribute(attribute:"plugin_publication_date", value:"2023/09/06");
script_set_attribute(attribute:"plugin_type", value:"remote");
script_set_attribute(attribute:"cpe", value:"cpe:/o:hitachienergy:rtu500_firmware:13.3.1");
script_set_attribute(attribute:"cpe", value:"cpe:/o:hitachienergy:rtu500_firmware:13.3.2");
script_set_attribute(attribute:"generated_plugin", value:"former");
script_end_attributes();
script_category(ACT_GATHER_INFO);
script_family(english:"Tenable.ot");
script_copyright(english:"This script is Copyright (C) 2023 and is owned by Tenable, Inc. or an Affiliate thereof.");
script_dependencies("tenable_ot_api_integration.nasl");
script_require_keys("Tenable.ot/ABB");
exit(0);
}
include('tenable_ot_cve_funcs.inc');
get_kb_item_or_exit('Tenable.ot/ABB');
var asset = tenable_ot::assets::get(vendor:'ABB');
var vuln_cpes = {
"cpe:/o:hitachienergy:rtu500_firmware" :
{"versionEndIncluding" : "13.3.2", "versionStartIncluding" : "13.3.1", "family" : "AbbRTU500"}
};
tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);