Lucene search

K
nessusThis script is Copyright (C) 2024 and is owned by Tenable, Inc. or an Affiliate thereof.TENABLE_OT_HONEYWELL_CVE-2023-5400.NASL
HistoryMay 02, 2024 - 12:00 a.m.

Honeywell Experion PKS, Experion LX, PlantCruise by Experion, Safety Manager, Safety Manager SC Heap-based Buffer Overflow (CVE-2023-5400)

2024-05-0200:00:00
This script is Copyright (C) 2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
4
honeywell
experion pks
experion lx
plantcruise
safety manager
safety manager sc
heap-based buffer overflow
cve-2023-5400
remote code execution
network exposure
firewall isolation
vpn
cisa
upgrade
versioning.

8.2 High

AI Score

Confidence

Low

0.0004 Low

EPSS

Percentile

9.1%

Server receiving a malformed message based on a using the specified key values can cause a heap overflow vulnerability which could lead to an attacker performing remote code execution or causing a failure.
See Honeywell Security Notification for recommendations on upgrading and versioning.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(502248);
  script_version("1.1");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/05/03");

  script_cve_id("CVE-2023-5400");

  script_name(english:"Honeywell Experion PKS, Experion LX, PlantCruise by Experion, Safety Manager, Safety Manager SC Heap-based Buffer Overflow (CVE-2023-5400)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"Server receiving a malformed message based on a using the specified
key values can cause a heap overflow vulnerability which could lead
to an attacker performing remote code execution or causing a failure.
See Honeywell Security Notification for recommendations on upgrading
and versioning.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  # https://process.honeywell.com/us/en/support/technical-publication?search=SN2024
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?899f3da1");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-24-116-04");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Honeywell fixed the reported issues and advises users to upgrade to version referenced in the Security Notice
or CVE record.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:

- Ensure the least-privilege user principle is followed.
- Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls and isolate them from business networks.
- When remote access is required, use secure methods, such as virtual private networks (VPNs),
recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2023-5400");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");
  script_cwe_id(122);

  script_set_attribute(attribute:"vuln_publication_date", value:"2024/04/25");
  script_set_attribute(attribute:"plugin_publication_date", value:"2024/05/02");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:honeywell:c300_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Honeywell");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Honeywell');

var asset = tenable_ot::assets::get(vendor:'Honeywell');

var vuln_cpes = {
    "cpe:/o:honeywell:c300_firmware:510" :
        {"versionEndExcluding" : "510.2hf14", "family" : "HoneywellExperion"},
    "cpe:/o:honeywell:c300_firmware:511" :
        {"versionEndExcluding" : "511.5tcu4hf4", "versionStartIncluding" : "511.0", "family" : "HoneywellExperion"},
    "cpe:/o:honeywell:c300_firmware:520.1" :
        {"versionEndExcluding" : "520.1tcu5", "versionStartIncluding" : "520.0", "family" : "HoneywellExperion"},
    "cpe:/o:honeywell:c300_firmware:520.2" :
        {"versionEndExcluding" : "520.2tcu4hf2", "versionStartIncluding" : "520.2", "family" : "HoneywellExperion"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);
VendorProductVersionCPE
honeywellc300_firmwarecpe:/o:honeywell:c300_firmware

8.2 High

AI Score

Confidence

Low

0.0004 Low

EPSS

Percentile

9.1%

Related for TENABLE_OT_HONEYWELL_CVE-2023-5400.NASL