Lucene search

K
nessusThis script is Copyright (C) 2023-2024 and is owned by Tenable, Inc. or an Affiliate thereof.TENABLE_OT_SIEMENS_CVE-2019-10920.NASL
HistorySep 21, 2023 - 12:00 a.m.

Siemens LOGO! 8 BM Improper Handling of Extra Values (CVE-2019-10920)

2023-09-2100:00:00
This script is Copyright (C) 2023-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
7
siemens logo! 8 bm
cve-2019-10920
decryption
port 10005/tcp
confidentiality
unauthenticated attacker
security vulnerability
tenable.ot scanner

CVSS2

5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

NONE

AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS3

7.5

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

NONE

Availability Impact

NONE

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

AI Score

7.4

Confidence

High

EPSS

0.005

Percentile

76.9%

A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Project data stored on the device, which is accessible via port 10005/tcp, can be decrypted due to a hardcoded encryption key. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(501674);
  script_version("1.5");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/09/04");

  script_cve_id("CVE-2019-10920");
  script_xref(name:"ICSA", value:"19-134-04");

  script_name(english:"Siemens LOGO! 8 BM Improper Handling of Extra Values (CVE-2019-10920)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS
variants) (All versions < V8.3). Project data stored on the device,
which is accessible via port 10005/tcp, can be decrypted due to a
hardcoded encryption key. The security vulnerability could be
exploited by an unauthenticated attacker with network access to port
10005/tcp. No user interaction is required to exploit this security
vulnerability. The vulnerability impacts confidentiality of the
device. At the time of advisory publication no public exploitation of
this security vulnerability was known.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/pdf/ssa-542701.pdf");
  script_set_attribute(attribute:"see_also", value:"http://www.securityfocus.com/bid/108382");
  script_set_attribute(attribute:"see_also", value:"https://seclists.org/bugtraq/2019/May/72");
  # http://packetstormsecurity.com/files/153122/Siemens-LOGO-8-Hard-Coded-Cryptographic-Key.html
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?c543cc8a");
  script_set_attribute(attribute:"see_also", value:"http://seclists.org/fulldisclosure/2019/May/44");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-19-134-04");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Siemens has released an update for the LOGO! 8 BM (update to v8.3) and recommends that customers update to the latest
version.. Notice that in order to update, a new hardware version is required.

To reduce risk, Siemens recommends that users apply defense-in-depth concepts, including protection concept outlined in
the system manual.

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate
mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the
environment according to SiemensҀ™ operational guidelines for industrial security and following the recommendations in
the product manuals.

Additional information on industrial security for Siemens devices can be found at:
https://www.siemens.com/industrialsecurity

For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security
Advisory SSA-542701");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:P/I:N/A:N");
  script_set_cvss_temporal_vector("CVSS2#E:POC/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:P/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2019-10920");

  script_set_attribute(attribute:"exploitability_ease", value:"Exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"true");
  script_cwe_id(321);

  script_set_attribute(attribute:"vuln_publication_date", value:"2019/05/14");
  script_set_attribute(attribute:"patch_publication_date", value:"2019/05/14");
  script_set_attribute(attribute:"plugin_publication_date", value:"2023/09/21");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:logo%218_bm_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:logo%218_bm_firmware:8");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2023-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Siemens");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Siemens');

var asset = tenable_ot::assets::get(vendor:'Siemens');

var vuln_cpes = {
    "cpe:/o:siemens:logo%218_bm_firmware" :
        {"family" : "LOGO!BM"},
    "cpe:/o:siemens:logo%218_bm_firmware:8" :
        {"versionEndExcluding" : "8.3", "family" : "LOGO!BM"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_WARNING);

CVSS2

5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

NONE

AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS3

7.5

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

NONE

Availability Impact

NONE

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

AI Score

7.4

Confidence

High

EPSS

0.005

Percentile

76.9%

Related for TENABLE_OT_SIEMENS_CVE-2019-10920.NASL